Punching shear at the column face
Maximum punching shear stress at the column perimeter compared with the crushing limit. Reference: EN 1992-1-1 6.4.5(3).
Open this sheet in Equation Pad Browse the Library

Example only. This sheet shows one way to set out the check. It is not endorsed by the bodies that publish the design codes and does not reproduce them. Check every clause, value and assumption against your own copy of the current edition of Eurocode 2 and its national annex before you use it, and have the result checked by a competent person. See the disclaimer.
The calculation, line by line
Every line below is typed into Equation Pad exactly as shown; the app typesets it, works out the value with its units and shows checks as TRUE or FALSE. Change any input and everything below it updates.
# Inputs
V_Ed := 850 kN
beta := 1.15
c_1 := 400 mm
c_2 := 400 mm
d := 240 mm
f_ck := 30 MPa
gamma_c := 1.5
# Check
u_0 := 2*(c_1 + c_2) =
v_Ed0 := beta*V_Ed/(u_0*d) = MPa
nu := 0.6*(1 - f_ck/(250 MPa)) =
v_Rd.max := 0.4*nu*f_ck/gamma_c =
v_Ed0 <= v_Rd.max =
How to use this example
- Click Open this sheet in Equation Pad. It opens as a new worksheet in your browser; nothing is installed.
- Change the inputs at the top to those of your project.
- Check the clauses and coefficients against the code, add your own checks, and save the sheet or export a PDF with your title block.
More Eurocode 2 sheets on slabs
- One-way spanning slab
- Two-way slab from moment coefficients
- Punching shear at the basic control perimeter
- Punching shear reinforcement
- Slab detailing rules
- Continuous one-way slab: moment and shear coefficients